Xtreme Safety FR Cable 2C-16 AWG-BC, Shielded FPLP (UL-NEC-IEC-332) Standard


For fixed installation typically in fire alarm and emergency lighting circuits where circuit integrity must be maintained. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.

Standards:

    FPLP (UL / NEC STANDARD       ) IEC-332 - 1

MAKE UP CHATECTERISTICS

11.1          Rate Voltage                450 / 750 Volts.

 

11.2          Conductor                    Class 1 Solid formed from plain annealed

copper complying with BS 6360 / IEC- 60228.

 

11.3             Insulation                   Fire Retardant PVC.

 

11.4            Identification               Numbered or Color coded

11.5            Laying up                    Laid with right hand direction of where necessary non

hygroscopic filler may be applied.

 

11.6          Screen                          100% BoPP / Al-Foil Tape

 

11.8          Over sheet                     Fire Retardant PVC.

 

11.9          Marking                        As per BS 7629- 1.

 

11.10     Conductor Resistance: As per BS 6360

11.11     Insulation Resistance : Insulation resistance between conductor

100 Meg Ohms / Km at 20 ºC when tested for One minutes at 500 V DC.

 

11.12     Temperature:                  -30 ‘C to + 125 ‘C.

 

11.13     Bending Radius:             6 x Overall Diameter.

11.14        Test Voltage:               2000V R.M.S for 5 minutes.

11.15        Outer Diameter:           8.0mm – 9.0mm


Model No : Xtreme Safety FR Cable 2C-16 AWG-BC, Shielded FPLP (UL-NEC-IEC-332) Standard